Powerware 9330 Power Supply User Manual


 
A --- 3 0
Powerware 9330 (10 kV A--40 kVA) Installation and Operation
164201300 REV. G 061502
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
G
ONELINE DRAWINGS OF UPS SYSTEM
1of1
031502
UPS CABINET
INVERTER
RECTIFIER
CB1
ST ATIC
SWITCH
BACKF EED
CONTACTOR
(K5)
RS --- 232
REMOTE EPO
BUILDING ALARMS
COMMUNICATIONS
SERVER
AC OUTPUT
TO
CRITICAL LOAD
OUTPUT
CONTACTOR
OUTPUT FILTER
(K3)
D
C
AC INPUT TO
UPS RECTIFIER
3 W IR E A --- B --- C
AC INPUT
TO BYPAS S
4 W IR E A --- B --- C
ROTATION
ROTATION
SEENOTE1
BA
NOTE 1: Remove jumper for dual feed.
(See Tables X, Y, and Z)
INPUT FIL TER
OPTIONAL
UPS SYSTEM WITH 208V INPUT AND OUTPUT, SINGLE OR DUAL FEED
POWERWARE 9330 (10 kVA---20 kVA)
POWERWARE 9330 (25 kVA---40 kVA)
INPUT
CONTACTOR
(K1)
BAT TERY
SWITCHES
INTERNAL
BATTERY
DC---DC
CONVERTER
(K2)
BATTERY
CABINET
EXTERNAL
BATTERY
BAT TERY
BREAKER
BAT TERY
BREAKER
GENERAL
PURPOSE RELAYS
CAN INTERFACE
X --- SLOT
INTERFACE
(Optional)
164201300---6
MAINTENANCE
BYPASS
SWITCH
(DUAL FEED)
AC INPUT TO
UPS RECTIFIER
(SINGLE OR DUAL FEED)
(SINGLE FEED)
CB2
FUSE
FUSE