PHYSICAL FEATURES AND REQUIREMENTS
164201300---3
A --- 2 5
Powerware 9330 (10 kV A--40 kVA) Installation and Operation
164201300 REV. G 061502
6. The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range: 0 --- 4 0 ˚C ( 3 2 --- 1 0 4 ˚F)
Recommended Operating Range: 20---25˚C ( 6 8 --- 7 7 ˚F)
Maximum Relative Humidity: 95%, noncondensing
The UPS ventilation requirements are shown in Table AC.
Table AC. Air Conditioning or Venti lation Req ui rements
During Full Load Operation
Po werware 9330 (10 kVA-- 40 kVA)
Ratings Input/Output Voltage
Heat Rejection*
BTU/hr ¢ 1000/hr (Kg---cal/hr)
208/208 2.4 (0.6)
10 KVA
480/208 3.1 (0.8)
480/480, 600/208 3.6 (0.9)
208/208 3.5 (0.9)
15 KVA
480/208 4.6 (1.1)
480/480, 600/208 5.3 (1.3)
208/208 4.7 (1.2)
20 KVA
480/208, 600/208 6.1 (1.5)
480/480 7.1 (1.8)
208/208 5.9 (1.5)
25 KVA
480/208, 600/208 7.7 (1.9)
480/480 8.9 (2.2)
208/208 7.1 (1.8)
30 KVA
480/208, 600/208 9.2 (2.3)
480/480 10.7 (2.7)
208/208 8.3 (2.1)
35 KVA
480/208, 600/208 10.8 (2.7)
480/480 12.5 (3.1)
208/208 9.5 (2.4)
40 KVA
480/208, 600/208 12.4 (3.1)
480/480 14.3 (3.6)