Powerware 9330 Power Supply User Manual


 
2-- 10
Powerware 9330 (10 kV A--40 kVA) Installation and Operation
164201300 REV. G 061502
2.2.4 Installing Optional Remote Battery Power Wiring to the
Powerware 9330 (25 kVA---40 kVA) UPS
If installing a remote battery system, perform the following procedure:
CAUTION:
When sizing battery system, do not exceed internal battery charger capabilities.
Refer to Chapter 15 “Specifications”, for maximum battery charger currents.
1. If not already removed, remove left front solid panel, and front vented panels
from the Powerware 9330 (25 kVA---40 kVA) UPS cabinet . Front panels are
secured with magnetic latches and are removed by pulling panel s straight
forward to disengage magnetic latches (see Figure 2---3).
NOTE: Remove UPS cabinet input, output, and remote battery input conduit landing
plate to punch conduit holes.
2. Ro ute battery cables to UPS remote battery terminal block. Refer to Appendix
A of this manual for wiring access information.
3. Connect positive, negative, and ground DC power wiring from external battery
source to the DC input and ground terminals in the UPS cabinet. Refer to
Appendix A of this manual for wiring and termination requirements and wiring
access information.
4. If permanently mounting the system, proceed to step 7; otherwise, proceed to
step 5.
5. Secure the UPS cabinet in position by lowering the leveling feet, until cabinet is
not resting on the casters and the cabinet is level.
6. If installing Battery and Options cabinets, repeat steps 1 through 10 in
paragraph 2.2.2 for Battery and Options cabinets and proceed to paragraphs
2.3 and 2.4; otherwise, proceed to paragraph 2.2.5.
7. Using retained hardware, reinstall shipping brackets previously removed to
front and rear of UPS cabinet with the angle facing outward.(see Figures 2---3
a n d 2 --- 4 ) .
8. If installing Battery and Options cabinets, repeat steps 1 through 10 in
paragraph 2.2.2 for Battery and Options cabinets and proceed to paragraphs
2.3 and 2.4; otherwise, proceed to step 9.
9. Secure cabinet to floor with contractor supplied hardware and proceed to
paragraph 2.2.5.