13--10
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A 092402
13.6 System Configuration
The System Configuration mode allows you to modify special functions in your
SSBM. These functions include pro g ramming of building alarms, customizing
building alarm messages, adjusting the nom inal output voltage, and scheduling
battery tests. The menus provided and their function are described in t his section.
13.6.1 System Configuration Mode Main Menu
When the System Configuration mode is selected with a terminal attached, you will
be prompted to enter the password for t his mode:
Please Enter Password:
The default password is POWER1. You may modify this password using the
change password function in the following menu. When the valid password is
entered, the main menu will be displayed:
Program Mode Main Menu
1. Program Building Alarms
2. Program Unit Name
3. Adjust Output Voltage
4. Change Password
5. Battery Test Setup
6. Modify Low Battery Time
7. Exit Program Mode
Enter Selection:
13.6.2 Program Building Alarms
This menu pro vides access to all the functions available in the system configuration
mode. If 1 is entered at the prom pt, you can p rogram the building alarm functions:
Program Building Alarms
1. Enable/Disable Default Functions
2. Customize Alarm Messages
3. Return to Main Menu
Enter Selection: