Powerware 9315s Power Supply User Manual


 
A---9
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A 092402
3
4
DESCRIPTION:
DRAWING NO: SHEET:
164201373---2
TYPICAL PARALLEL CAPACITY/
REDUNDANT SYSTEM WITH SSBM
COMMON BATTERY SYSTEM
2of2
1
1
1
1
2
5
5
NOTE: 1. Accommodates one to eight UPMs. Four
UPM system shown.
2. The input transformer cabinet may be
installed on either the left or the right
side of the UPM cabinet.
3. Refer to the Powerware 9315 UPS
Installation manual provided with the
UPMs, for UPM, battery, and optional
input transformer installation information.
4. Actual SSBM physical arrangement and
cable connection locations may differ
from that shown. See drawings
164201373---11 and 164201373---12
for details.
1
3
4
UTILITYPOWER INPUTTOUPM
SSBMOUTPUTTOCRITICALLOAD
UTILITYPOWERINPUTTOBYPASSBUS
5
POWERNETDUALREDUNDANTNETWORK
SSBMINTERFACE-- TERMINALBLOCKTB1
UPMINTERFACE-- TERMINALBLOCKTB1
2
UPMOUTPUTTOSSBMINPUT
FOR9315 --625/750UPMONLY:
ALSOINCLUDES DUALREDUNDANT
NETWORKPOWERSUPPLY
SBM INTERFACE--TB7
UPMINTERFACE --CANA&CANB
*SeeTableOofAppendixAforUPM
OutputConductorSizing.