Powerware 9315s Power Supply User Manual


 
A --- 44
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A 092402
Table O. UPM Output-to-SSBM Cable and Conduit Configurations: Based on UPM Manuals
UPM Output-to-SSBM Cable Configuration
MinimumConductorSize,3,(1)Neutral,(1)Gnd
Max No. of UPMsConnectable to each SSBM
(Based on UPM-to-SSBM Cable Con figuration
9315
Model - kVA/kW
Output
Voltage
Output
Current
Conductor Size
(AWG or kcmil)
Number of
Conductors per
and Neutral
Number and
Size of Conduit
(in inches)
Model 2500 Model 3000 Model 4000
200 --- 200/160 400 290 4/0 2 2---2.0 7 7 7
225 --- 225/180 208 625 350 3 3---2.0 4 4 4
225 --- 225/180 480 271 3/0 2 1---2.0 7 7 7
300 --- 225/180 480 271 3/0 2 1---2.0 7 7 7
300 --- 225/180 600 217 350 1 1---2.0 8 8 8
300 --- 300/240 208 830 500* 3 3---3.0 4 4 4
300--- 300/240 480 360 250 2 2---2.0 7 7 7
300--- 300/240 600 289 4/0 2 2---2.0 7 7 7
250 --- 200/160 400 290 4/0 2 2---2.0 7 7 7
250 --- 250/200 400 360 250 2 2---2.0 7 7 7
400 --- 300/240 400 433 3/0 3 3---2.5 4 4 4
400 --- 400/320 400 577 250 3 3---2.5 4 4 4
500 --- 400/320 208 1110 600* 5 5---3.0 2 2 2
500 --- 400/320 480 480 250 3 3---3.0 4 4 4
500 --- 500/400 480 601 350 3 3---3.0 4 4 4
500 --- 500/400 600 601 350 3 3---3.0 4 4 4
625 --- 500/400 400 722 300 4 3---3.0 3 3 3
625 --- 500/450 400 722 300 4 3---3.0 3 3 3
625 --- 625/500 400 902 500 4 3---3.5 3 3 3
625 --- 626/562 400 902 500 4 3---3.5 3 3 3
750 --- 625/500 480 752 500 3 3---3.0 4 4 4
750 --- 625/500 600 601 350 3 3---3.0 4 4 4
750 --- 625/562 480 752 500 3 3---3.0 4 4 4
750 --- 625/562 600 601 350 3 3---3.0 4 4 4
750 --- 750/600 480 902 400 4 3---3.5 3 3 3
750 --- 750/600 600 722 500 3 3---3.0 4 4 4
750 --- 750/675 480 902 400 4 3---3.5 3 3 3
750 --- 750/675 600 722 500 3 3---3.0 4 4 4
DESCRIPTION:
DRAWING NO: SHEET:
164201373---14
UPM OUTPUT-TO-SSBM CABLE AND
1of2
CONDUIT CONFIGURATIONS
NOTES:
1. * = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements
between the UPS and its output transformer.