Powerware 9315s Power Supply User Manual


 
4-- 3
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A 092402
NOTE: Before installing an RMP, be sure you have prepared the SSBM according to
the instructions in Chapter 2.
4.2 To i ns ta ll a n R M P:
1. Securely mount the RMP(s).
2. Install wiring from the RMP using ½-in. conduit through the cable entry panels
in the top of the S SBM control section (refer to the enclosed switchboard
vendor drawings for the location of the conduit landing plate).
3. In the spare parts kit, l ocate the RMP adapter cable assembly
(see Figure 4---2) . Mate the DB---9 connector on the back of the terminal block
to the DB---9 connector (Port 1) on the Customer Interface Panel of the SSBM
(refer to Drawing 164201373---4 in Appendix A). Use two screws from the
spare parts kit to secure the terminal block bracket to the Customer Interface
Panel.
Connect to
Po rt 1 (DB --- 9) on
Customer Interface Panel
TERMINAL
BL OCK
FUSE
(TB3)
Figure 4---2. Terminal Block Bracket