Toshiba G3 TOSVERT-130 Power Supply User Manual


 
31
11.1
11.111.1
11.1
Read
ReadRead
Read-
--
-Only Registers
Only RegistersOnly Registers
Only Registers
Register Bit Function Bank Mask Adjustment Range Multiplier
01 09
word Reserved
0A word RX terminal analog input
value
0 FFFF 0000 ~ 7FFF (-100% ~ 0%)
7FFF ~ FFFF (0% ~ 100%)
1
0B word Frequency command
monitor
0 FFFF
0000 9C40
(0.00 400.00 Hz)
0.01
0C word
Input voltage monitor(Note 1)
0 FFFF 0 ~ 255% 0.1
0D word Output terminal status
monitor
0 00FF Refer to Table 4 (page 32)
0E word Inverter Status 1 0 FFFF Refer to Table 5 (page 32)
0F word Inverter Status 2 0 00FF Refer to Table 6 (page 32)
10 word Present trip 0 00FF
11 high
byte
4th Past trip (most recent) 0 7F00
low
byte
3rd past trip 007F Refer to section 11.3 for fault
codes
12 high
byte
2nd past trip 0 7F00
low
byte
1st past trip (oldest) 007F
13 word Pre-compensation output
frequency
0 FFFF
0000 9C40
(0.00 400.00 Hz)
0.01
14 word Post-compensation output
frequency
0 FFFF
0000 9C40
(0.00 400.00 Hz)
0.01
15 word Torque current monitor 0 FFFF
(Note 2)
0.01
16 word Excitation current monitor 0 00FF
00 FF (0 ~ 255%)
1
17 word PID feedback value 0 FFFF
(Note 2)
0.02
18 word Motor overload ratio 0 FFFF 0 ~ 65535 100/65535
19 word Inverter overload ratio 0 FFFF 0 ~ 65535 100/65535
1A word DBR overload ratio 0 FFFF 0 ~ 65535 100/65535
1B word Input power (%) 0 FFFF 0 ~ 6553.5 0.1
1C word Input power (kW) 0 FFFF
(Note 3)
1D word Output power (%) 0 FFFF
(Note 2)
0.1
1E word Output power (kW) 0 FFFF
(Note 2, Note 3)
1F, 20 word Reserved
21 word Input / output power units 0 0008 0000: 0.01kW
0008: 0.1kW
22 word Command mode status 0 0003 0000: terminal
0001: panel
0002: option
0003: RS232C
23 word Frequency mode selection
status
0 000C 0000: terminal
0004: panel
0008: option
000C: RS232C
24 low
byte
Profibus interface card
software revision
high
byte
Profibus interface card
software version
25 word Output current (amps)
FFFF 0.0 ~ 6553.5 A 0.1
(Note 1) These monitor voltage units are not affected by the setting of VOLTAGE UNITS SELECTION in
GROUP:UTILITY PARAMETERS; they are always in units of %.
(Note 2) These registers use signed data (data values larger than 7FFF
H are negative). If the register data is
8000
H or larger, the actual value can be obtained by: actual value = - [FFFFH - (register data) + 1].