Toshiba G3 TOSVERT-130 Power Supply User Manual


 
33
11.2
11.211.2
11.2
Read/Write Registers
Read/Write Registers Read/Write Registers
Read/Write Registers
11.2.1
11.2.111.2.1
11.2.1
GROUP:FUNDAMENTAL PARAMETERS #1
GROUP:FUNDAMENTAL PARAMETERS #1GROUP:FUNDAMENTAL PARAMETERS #1
GROUP:FUNDAMENTAL PARAMETERS #1
Register Function / Title Bank Mask Adjustment Range Multiplier
26
MAXIMUM OUTPUT
FREQUENCY (
)
0 / 1 FFFF
0BB8 9C40 (30.00400.00)
0.01
27
BASE FREQUENCY #1
0 / 1 FFFF
09C4 9C40 (25.00400.00)
0.01
28
BASE FREQUENCY
VOLTAGE SELECT (
)
0 / 1 0030 0000: Input voltage level (0)
0020: Automatic setting (1)
0030: Stationary setting (2)
29
MAXIMUM OUTPUT
VOLTAGE #1
0 / 1 FFFF
0000 0258 (0 600)
1
2A
REVERSE OPERATION
DISABLE SELECT
0 / 1 0020 0000: Reverse allowed (0)
0020: Reverse not allowed (1)
2B
UPPER LIMIT FREQUENCY
0 / 1 FFFF 0000 ~ Fmax 0.01
2C
LOWER LIMIT FREQUENCY
0 / 1 FFFF
0000 UL, Fmax
0.01
2D
VOLTS PER HERTZ
PATTERN (
)
0 / 1 000F 0000: Constant torque (1)
0001: Variable torque (2)
0002: Auto. torque boost (3)
0006: #3 w/ auto. energy savings (4)
000A: Vector control (5)
000E: #5 w/ auto. energy savings (6)
2E 1, 2
VOLTAGE BOOST #1
0 / 1 FFFF
0000 012C (0.0 30.0)
0.1
2F
ACCELERATION TIME #1
0 / 1 FFFF
0001 EA60 (0.01~ 600.00)
0001 EA60 (0.1~ 6000.0)
0.01
0.1
30
DECELERATION TIME #1
0 / 1 FFFF
0001 EA60 (0.01~ 600.00)
0001 EA60 (0.1~ 6000.0)
0.01
0.1
31
ACC/DEC PATTERN #1
SELECTION
0 / 1 0030 0000: Linear (0)
0010: Self-adjusting (1)
0020: S-Pattern #1 (2)
0030: S-Pattern #2 (3)
32
ACCEL/DECEL PATTERN
ADJUST LOW
0 / 1 00FF
0003 ~ 00FD (0 50) (Note 1)
1
33
ACCEL/DECEL PATTERN
ADJUST HIGH
0 / 1 00FF
0003 ~ 00FD (0 50) (Note 1)
1
Note 1: Register data = (desired setting x 5 + 3), converted to hexadecimal