Toshiba G3 TOSVERT-130 Power Supply User Manual


 
44
Register Function / Title Bank Mask Adjustment Range Multiplier
135
UNDERVOLTAGE TRIP
SELECTION
0 / 1 0080 0000: Trip disabled (0)
0080: Trip (during run) (1)
136
UNDERVOLTAGE DETECT
TIME
0 / 1 FFFF
0000 03E8 (0.00 10.00)
0.01
137
LOW CURRENT DETECT
SELECTION
0 / 1 0008 0000: Trip disabled (0)
0008: Trip on detection (1)
138
LOW CURRENT DETECT
LEVEL
0 / 1 00FF
0000 0064 (0 100)
1
139
LOW CURRENT DETECTION
TIME
0 / 1 00FF
0000 00FF (0 255)
1
140
OUTPUT SHORT-CIRCUIT
DETECTION SELECT
0 / 1 0003 0000: Standard motor (0)
0001: High-speed motor (1)
0002: Positioning use (standard
motor) (2)
0003: Positioning use (high-speed
motor) (3)
141
OVERTORQUE TRIP
SELECTION
0 / 1 0040 0000: Trip disabled (0)
0040: Trip enabled (1)
142
OVERTORQUE TRIP LEVEL
0 / 1 00FF
0000 00C8 (0 200)
1
143
FAULT TRIP EEPROM
SAVE ENABLE
0 / 1 0002 0000: Data cleared when powered
OFF (0)
0002: Data retained when powered
OFF (1)
144
COOLING FAN CONTROL
SELECTION
0 / 1 0004 0000: Automatic (temperature
detection) (0)
0004: Always ON (1)
145
CUMULATIVE RUN TIMER
ALARM SETTING
0 / 1 FFFF
0000 C34B (0.00 999.90)
0.02