Toshiba G3 TOSVERT-130 Power Supply User Manual


 
32
(Note 3) If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is
0.01. If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier
is 0.1. These values are automatically set according to the inverter’s capacity.
Table 4: Output Terminal Status Monitor (register 0D)
Lower
Byte
Bit Output Terminal 0 1 Single-Bit
Read Mask
bit 0 unused (always 0)
bit 1 unused (always 0)
bit 2 FAN OFF ON 0004
bit 3 FL FLB-FLC shorted FLA-FLC shorted 0008
bit 4 MS relay OFF ON 0010
bit 5 OUT (option) OUTB-OUTC shorted OUTA-OUTC shorted 0020
bit 6 RCH RCHA-RCHC open RCHA-RCHC shorted 0040
bit 7 LOW LOWA-LOWC open LOWA-LOWC shorted 0080
Table 5: Inverter Status 1 (register 0E)
Lower
Byte
Bit Inverter Status 0 1 Single-Bit
Read Mask
bit 0 running (acc/dec)
running 0001
bit 1 unused (always 0)
bit 2 forward / reverse reverse forward 0004
bit 3 acc/dec #1/#2 acc/dec #1 acc/dec #2 0008
bit 4 for inverter use
bit 5 for inverter use
bit 6 for inverter use
bit 7 jog/normal mode normal (acc/dec) jog mode 0080
Upper
Byte
Bit Inverter Status 0 1 Single-Bit
Read Mask
bit 0 feedback ON/OFF OFF feedback active 0001
bit 1 DC inj. braking OFF DC inj. braking active 0002
bit 2 V/F #1/#2 V/F #1 V/F #2 0004
bit 3 coasting not coasting coasting 0008
bit 4 emergency off not in emergency off in emergency off 0010
bit 5 for inverter use
bit 6 for inverter use
bit 7 for inverter use
Table 6 : Inverter Status 2 (register 0F)
Upper
Byte
Bit Inverter Status 0 1 Single-Bit
Read Mask
bit 0 accelerating not accelerating accelerating 0001
bit 1 decelerating not decelerating decelerating 0002
bit 2 for inverter use
bit 3 retry not retrying retrying 0008
bit 4 running (including DC
injection braking)
stopped running 0010
bit 5 for inverter use
bit 6 for inverter use
bit 7 tripped not tripped tripped 0080