Toshiba G3 TOSVERT-130 Power Supply User Manual


 
48
11.2.9
11.2.911.2.9
11.2.9
GROUP:FEEDBACK CONTROL PARAMET
GROUP:FEEDBACK CONTROL PARAMETGROUP:FEEDBACK CONTROL PARAMET
GROUP:FEEDBACK CONTROL PARAMETERS
ERSERS
ERS
Register Function / Title Bank Mask Adjustment Range Multiplier
190
FEEDBACK CONTROL
SELECTION
0 / 1 0060 0020: No feedback (0)
0040: PID control (1)
0060: Speed feedback (2)
191 1, 2
FEEDBACK INPUT
SIGNAL SELECTION
0 / 1 001C 0004: RR input (1)
0008: IV input (2)
000C: RX input (3)
0010: PG feedback (4)
0014: RS232C input (5)
0018: Communication/12-bit binary
interface board (6)
001C: BIN input (7)
192
PROPORTIONAL
GAIN
0 / 1 00FF
0001 00FF (0.01 2.55)
0.01
193
INTEGRAL GAIN
0 / 1 FFFF
0001 8CA0 (0.01 360.00)
0.01
194
ANTI-HUNTING
GAIN
0 / 1 00FF
0000 00FF (0.0 25.5)
0.1
195
LAG TIME
CONSTANT
0 / 1 00FF
0000 00FF (0 255)
1
196
PID LOWER LIMIT
FREQUENCY
0 / 1 FFFF
0 Fmax
0.01
197
PID DEVIATION LIMIT
SELECTION
0 / 1 0080 0000: No PID deviation limit (0)
0080: PID deviation limited (1)
198 1
PID DEVIATION
UPPER LIMIT
0 / 1 00FF
0000 0032 (0 50)
1
199
PID DEVIATION
LOWER LIMIT
0 / 1 00FF
0000 0032 (0 50)
1
19A
PG INPUT: NUMBER OF
PULSES
0 / 1 FFFF
0001 270F (1 9999)
1
19B
PG INPUT: NUMBER OF
PHASES
0 / 1 0001 0000: Single-phase input (1)
0001: Two-phase input (2)
19C
DROOPING CONTROL
ENABLE
0 / 1 0002 0000: OFF (0)
0002: ON (1)
19D 1
DROOPING CONTROL
AMOUNT
0 / 1 00FF
0000 0064 (0 10.0)
0.1
19E
OVERRIDE CONTROL
SELECTION
0 / 1 0007 0000: OFF (0)
0001: FCRR (1)
0002: FCIV (2)
0003: FCRX (3)
0004: FCPG (4)
0005: FCPNL (5)
0006: FCOPT (6)
0007: FCMLT (7)
19F 7
OVERRIDE
MULTIPLIER INPUT
SELECTION
0 / 1 0038 0000: Reference (0)
0008: KRR (1)
0010: KIV (2)
0018: KRX (3)
0020: KBIN (4)
1A0
OVERRIDE CHANGE
MULTIPLIER
0 / 1 FFFF
FC18 03E8 (-100.0 100.0)
0.1
1A1
1CF
Reserved