8300 Troubleshooting
Reset All Timers
Disable Outputs
Enable Communications
Present Sign-on Message to Diagnostic Terminal
7.2.4 Performing a Hard Reset
A ‘Hard Reset’ clears the TankGate’s database. The following procedure describes the
steps necessary to perform a Hard Reset:
1. Set the ID DIP switch to 15 (all switches Closed/On). This action initiates the Hard
Reset Procedure.
Figure 7-1: Set the ID DIP switch to 15
2. Press the Reset button
Figure 7-2: Switches SW3 on the TankGate motherboard
3. The TankGate will perform its memory test. When it has completed the memory
test, all LEDs will be on.
ID = 15