Appendix TankGate Interface
ii Installation and Operations Manual
1.2.1 Modbus Map
Address Type Number Parameter Data Type
5000
LJ2000 0 Command CODED
5001
LJ2000 0 Level REAL
5003
LJ2000 0 Temp REAL
5005
LJ2000 0 Value REAL
5007
LJ2000 0 Status HEX
5008
LJ2000 0 PntStatus IHEX
5009
LJ2000 0 Elapse TIME
There are a total of 50 GPE points. There are a total of 11 registers available per gauge. The addresses are sequential. The addresses range from
5000 to 5550
4000
SCALER 0 Value REAL
4002
SCALER 0 Value1 INTEGER
4003
SCALER 0 PntStatus UBYTE
4004
SCALER 0 Elapse TIME
4006
SCALER 1 Value REAL
4008
SCALER 1 Value1 INTEGER
4009
SCALER 1 PntStatus UBYTE
4010
SCALER 1 Elapse TIME
There are a total of 16 SCLAER points. There are a total of 11 registers available per SCALER point The addresses are sequential. The addresses
range from 4000 to 4095
1000
IREG 0 Value1 UINTEGER
1001
IREG 0 Value2 UINTEGER
1002
IREG 0 Value3 UINTEGER
1003
IREG 0 Value4 UINTEGER
1004
IREG 0 Value5 UINTEGER
1005
IREG 0 Value6 UINTEGER
1006
IREG 0 Value7 UINTEGER
1007
IREG 0 Value8 UINTEGER
1008
IREG 0 Value9 UINTEGER
1009
IREG 0 Value10 UINTEGER
1010
IREG 0 Value11 UINTEGER