Cooper Lighting S280-79-10 Power Supply User Manual


 
The UDP function allows the Form 5 control to become a
switch control to provide indication of overcurrent trip con-
ditions without issuing an overcurrent trip signal. The con-
trol is in the recloser mode when the feature is in the OFF
position, and in the switch mode when the feature is
ACTIVE.
While in the switch mode, all automatic open and close
operations of the recloser (including overcurrent voltage
and frequency) are blocked. Fault targeting, metering,
alarms, and event recording functions are active.
This non-tripping fault indication state is initiated via a
operator panel pushbutton (labeled SWITCH MODE), dig-
ital SCADA, or discrete SCADA. The UDP feature has
local indication at the operator panel (LED), digital indica-
tion, and remote indication via status contacts on the Dis-
crete Interface (DIF) module 1.
S280-79-10
21
!
SAFETY
FOR LIFE
Figure 21.
Interface software Switch Mode settings.
GND TRIP
BLOCKED
NON
RECLOSING
SUPERVISORY
BLOCKED
COLD LOAD
PICKUP
BLOCKED
BATTERY
TEST
FAST
TRIPS
DISABLED
ALTERNATE
PROFILE
NO. 1
ALTERNATE
PROFILE
NO. 2
SWITCH
MODE
Figure 20.
Function/Indication pushbuttons for the Form 5
equipped with the UDP accessory.
FORM 5 UNIVERSAL DEVICE PROTECTION (UDP) CONTROL
CONTROL OK
AC POWER
ABOVE MIN TRIP
REVERSE POWER FLOW
RECLOSER MALFUNCTION
CHECK BATTERY
BUSHINGS 1-2 FAULT TARGET
BUSHINGS 3-4 FAULT TARGET
BUSHINGS 5-6 FAULT TARGET
GROUND FAULT TARGET
SENSITIVE-GROUND FAULT TARGET
AØ
BØ
CØ
RECLOSER CLOSED
RECLOSER OPEN
CONTROL LOCKOUT
BACK
NEXT
LAMP
TEST
CHANGE
RESET
TARGETS
RESET
MAX CURRENT
GND TRIP
BLOCKED
NON
RECLOSING
SUPERVISORY
BLOCKED
COLD LOAD
PICK UP
BLOCKED
BATTERY
TEST
FAST
TRIPS
DISABLED
ALTERNATE
PROFILE
NO. 1
ALTERNATE
PROFILE
NO. 2
SWITCH
MODE
HOT LINE
TAG
ON
OFF
TX 3
RX 3
CLOSE
TRIP
(LOCKOUT)
KYLE
®
FORM 5/UDP
RECLOSER CONTROL
RS232
TX 2
RX 2
SOURCE
VOLTAGE
XØ
YØ
ZØ
LOAD
VOLTAGE
Figure 22.
Form 5/UDP Operator Panel.