Fluke 435 Power Supply User Manual


 
Fluke 434/435
Users Manual
23-12
Mains Signaling Measurement are based on: either the corresponding 10/12-cycle r.m.s. value
interharmonic bin or the rms of the four nearest 10/12-cycle rms value
interharmonic bins per IEC 61000-4-30 Limit setup for Monitor mode follows
EN50160 “Meistercurve”
Time Synchronisation Optional GPS430 timesync module provides time uncertainty 20 ms or 16.7
ms
2
for time tagging of events and time aggregated measurements. When
synchoronisation becomes unavailable, time tolerance is 1-s/24h
WIRING COMBINATIONS
3Ø WYE Three phase four wire system WYE
3Ø DELTA Three phase three wire system Delta
1Ø + NEUTRAL Single phase with neutral
1Ø SPLIT PHASE Split phase
1Ø IT NO NEUTRAL Single phase system with two phase voltages without neutral
3Ø IT Three phase system without neutral WYE
3Ø HIGH LEG Four wire three phase Delta system with center tapped high leg
3Ø OPEN LEG Open delta three wire system with 2 transformer windings
2-ELEMENT Three phase three wire system without current sensor on phase L2 / B (2 Watt
meter method)
2½-ELEMENT Three phase four wire system without voltage sensor on phase L2 / B
GENERAL
Case
Design Rugged, shock proof with integrated protective holster
Drip and dust proof IP51 according to IEC60529 when used in tilt stand position
Shock and Vibration Shock 30g, Vibration: 3g Sinusoid, Random 0.03g
2
/Hz according to MIL-PRF-
28800F Class 2
Display Bright Full-Color LCD with CCFL backlight, 80cd/m
2
Size 115.2 x 86.4 mm
Resolution 320 x 240 pixels
Contrast and
brightness
User adjustable, temperature compensated