Fluke 435 Power Supply User Manual


 
Specifications
Electrical Measurements23
23-15
ELECTRO MAGNETIC COMPATIBILITY (EMC)
Compliance with
Fluke 434/435, including standard accessories, conforms to the EEC
directive 2004/108/EC for EMC immunity as defined by EN-61326-
1:2006 , with the addition of the table below
Frequency No Visible Disturbance Disturbance < 0.5 % Disturbance < 10 %
80 – 400 MHz All ranges
400 – 600 MHz All other ranges 125 V range
600 MHz – 1 GHz All ranges
1.4 – 2 GHz
(3V/m)
All ranges
2 – 2.7 GHz
(1V/m)
All ranges
The Analyzer is susceptible for RF fields with a field strength of 10 V/m, between 400 and 600 MHz
(Performance criteria B).
1
depending clamp scaling, volt scaling 1:1
2
50Hz/60Hz nominal frequency according to IEC 61000-4-30
3
Add clamp accuracy
4
The logger and Mains Signaling function are optional for the Fluke 434 and standard
available on the Fluke 435
5
Measured on reference voltage input A/L1
6
Maximum time 9999 hours
7
Estimated duration
8
Add ±(n-1) x 2.5° for Amp. when using i430flex