GE AF-300 Power Supply User Manual


 
LED
Data Factory Customer
Display Setting Description Setting Setting
6-9
F_17 DC BRAKE (Operation Selection)
This selects the DC brake operation to active or inactive 0
0: Inactive - (Regenerative braking only)
1:
Active - (DC braking after regenerative braking)
*F_18 0 t o 6 0
DC BRAKE (Starting Frequency)
Sets the frequency to start DC injection brake 0 Hz
operation during deceleration.
*F_19 0 to 1 0 0
DC BRAKE (Brake Level)
Sets the output braking level (brake output) for the DC 50%
injection brake. The braking strength will
vary depending on the characteristics of the motor.
*F_20 0.00 to 30
DC BRAKE (Braking Time)
Sets the operation time for the DC injection brake. 0.5s
1
If the data is set to "0", the frequency will be 0.2 Hz.
The Drive braking function cannot be substituted
for mechanical means. Attempting to do so may
result in injury.
Starting Range Unit Setting Step
Starting Frequency 0
1
to 60
Hz 1 Hz
Braking Level
0 to 100 % 1%
Braking Time s
0.00 to 9.99
10.0 to 30.0
0.01
0.1
Operating
Speed
Operating
Speed
Time
Time