GE AF-300 Power Supply User Manual


 
LED
Data Factory Customer
Display Setting Description Setting Setting
6-13
F_33 BRAKING TORQUE SELECTION 0
This sets the limit level for braking torque in accordance
with the brake being used.
0 Low (no Dynamic Braking option)
1 High (with Dynamic Braking option)
NOTE: Always connect an extra braking resistor. Contact
GE Fuji Technical Services for proper brake
resistor option selection.
*F_34 -400
BIAS FREQUENCY 0
to This function adds the bias frequency offset to the analog
+400 reference frequency to produce the output frequency.
The setting range is between -400 to +400Hz in
steps of 1Hz.
*The bias frequency is only active when the frequency
setting function F_01 = 1
If the bias frequency has been set, the Drive will operate
when an operation command is given, even if the analog
frequency is zero.