GE AF-300 Power Supply User Manual


 
LED
Data Factory Customer
Display Setting Description Setting Setting
6-25
F_76 0.00 to 50 MOTOR 1 (%X Setting) Std. 4-pole
This function displays the leakage reactance X1 of the motor
motor in terms of percentage, and is set manually
The data can be overwritten and changed automatically
by automatic tuning using function F_74, or by setting
the motor capacity, rated current and no-load current
using functions F_70 to F_72.
Calculation Formula for %X1
X1 + X2 = Xm/ (X2 + Xm) + cable X
%X1 = x 100 [%]
V / ( 3 • I)
X1: Primary inductance of motor 1[Ohm]
X2: Secondary inductance of motor 1 [Ohm]
Xm
: Mutual inductance of motor 1 [Ohm]
Cable X: [Ohm]
V: Rated voltage of motor
I: Rated current of motor
: Value calculated for Y connection
%R1 and %X1 should be set to values which are appropriate
for the motor being used. The motor may not operate
correctly if these values are not set correctly, which could
result in accidents.
*F_77 000 to 999
TORQUE LIMITING RESPONSE
(At Constant Speed) 369
*F_78 000 to 999
TORQUE LIMITING RESPONSE
(During Acceleration/Deceleration 394
P – Represented by the Hundreds Digit (Gain Value)
I – Represented by the Tens and Units Digit (Time Constant)
F_79
OPTION SELECTION 0
This function sets whether an option is being used or
not, and also what type of option is being used if any.
0: No Options
1: DI option card used
2: DI/O option card used
3: RS option card used
NOTE: For details on setting specifications when
using an option card, refer to the instruction
manual which is supplied with the option card.
000 999
to
P I P I
(Quick) (Slow)
0 0 · · · 9 9
P
I
0 (Low)
·
·
9 (High)