IBM RS/6000 SP Switch User Manual


 
Step 0600-005
You performed the recommended action in Table 1-4 on page 1-10.
1. Component replaced or reseated.
2. Check the yellow switch supervisor LED for an On or flashing condition.
3. Is the yellow switch supervisor LED On or flashing?
v If yes, return to “Step 0600-004” on page 1-10 and continue service with the next highest priority.
v If no, go to “Step 0620-021” on page 1-27.
Step 0600-006
Perspectives indicated a shutdown temperature condition and Table 1-3 on page 1-9 directed you to this
step.
Temperature is out of specified range; however, no serious electrical current or fan speed problems have
been detected.
1. Check for airflow blockage at air intakes and exhaust of the switch assembly and system frame. Also,
check air temperatures around the frame, looking for sources of abnormally high temperatures (above
40 C or 104 F).
2. Is there an obvious airflow blockage or abnormally high temperature source near air intakes?
v If yes, go to “Step 0600-009” on page 1-12.
v If no, go to “Step 0600-007” on page 1-12.
Figure 1-3. SP Switch2 Chassis Assembly
Switch environment (MAP 0600)
Chapter 1. Maintenance Analysis Procedures (MAPs) 1-11