Liebert DS Network Card User Manual


 
Liebert DS Dimensions and Weights
13
Figure 8 Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton),
all compressor models
Table 5 Weights for downflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Compressor Type
Dry Weight - lb. (kg),
Approximate
Model 028, 035, 042
Semi-Hermetic Compressor
Water/Glycol 1930 (877)
GLYCOOL/Dual-Cool 2080 (945)
Scroll or Digital Scroll Compressor
Water/Glycol 1780 (809)
GLYCOOL/Dual-Cool 1930 (877)
33"
(838mm)
Notes: Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
Front View
Top View
Air Inlet Opening
Shaded area indicates a
recommended minimum
clearance for component
access.
86"
(2184mm)
DPN000894
Rev. 3
2"
(51mm)
85" (2159mm)
76"
(1930mm)
35"
(889mm)
56-7/8"
(1445mm)
Opening
3/4"
(19mm)
Bezels
Secondary Entrance
High Volt Connection(s)
Condenser Cleanout Access
Secondary Entrance
Low Volt Connections
24-3/8"
(619mm)
Opening
15"
(381mm)
24"
(610mm)
Required for
condenser cleanout
Minimum required
for filter replacement
34" (864mm)
Secondary Condenser
Fluid Piping Entrance