Liebert DS Dimensions and Weights
18
Figure 13 Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 105kW (30 ton), all
compressor models
Table 10 Weights for downflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models
Compressor Type
Dry Weight, lb (kg) approximate
Model 105
Semi-Hermetic Compressor
Water/Glycol 3410 (1550)
GLYCOOL/Dual-Cool 3770 (1714)
Scroll Compressor
Water/Glycol 3290 (1495)
GLYCOOL/Dual-Cool 3650 (1659)
35"
(889mm)
132"
(3353mm)
76"
(1930mm)
131"
(3327mm)
34"
(864mm)
Shaded area indicates a
recommended minimum
clearance for component
access.
15"
(381mm)
3/4"
(19mm)
24-3/8"
(619mm)
102-13/16"
(2611mm)
Secondary Condenser
Fluid Entrance
Air Inlet Opening
Opening
Opening
Bezels
Secondary Entrance
Low Volt Connections
Minimum required
for filter replacement
Secondary Entrance
High Volt Connection(s)
Top View
Front View
Notes: Filters are accessible
only through top of unit.
Downflow electrical
connections can be made
from top or bottom of unit.
Condenser Cleanout Access
33"
(838mm)
24"
(610mm)
Required for
condenser cleanout
DPN001013
Rev. 2