Piping
77
Table 47 Line charges - refrigerant per 100 ft (30m) of Type “L” copper tube
O.D. Liquid Line, lb (kg)
1/2" 7.3 (3.3)
5/8" 11.7 (5.3)
7/8" 24.4 (11.1)
1-1/8" 41.6 (18.9)
Table 48 Outdoor condenser approximate refrigerant charge lb (kg) per circuit
Model
Fan
Speed
Lee-Temp
(includes receiver)
165 5 (2.3) 27 (12.3)
205 7 (3.2) 38 (17.2)
251 10 (4.6) 38 (17.20
308 11 (5.0) 58 (26.3)
415 15 (6.8) 75 (34.0)
510 30 (13.6) 149 (67.6)
143 17 (8) 64 (29)
214 23 (10 81 (37)
286 29 (13) 98 (44)
409 36 (16) 129 (59)
477 24 (11) 80 (36)
572 57 (26) 196 (89)