Liebert DS Dimensions and Weights
29
Figure 24 Floor stand dimensions—downflow, 105kW (30 ton) models
Table 21 Floor stand and floor planning dimensions—downflow, 105kW (30 ton) models
Height, in. (mm)
C* D turning vane
9 (229) 4 (111)
12 (305) 7 (187)
15 (381) 10 (264)
18 (457) 13 (340)
21 (533) 16 (416)
24 (610) 19 (492)
D
DPN001059
REV 1
NOTE: Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floor stand 1" (25mm).
* Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C.
Gussets supplied
on floor stands 12" (305 mm)
tall and greater
Turning vane air outlet
Optional turning vane can be field-installed
in supply air discharge opening for front or
rear air discharge.
Supply air
discharge
opening
Optional turning vane
shown as front air discharge.
Supply air
discharge opening
33"
(838mm)
34-1/2"
(876mm)
(with feet)
132-1/2"
(3366mm) (with feet)
26"
(660mm)
91-3/4"
(2330mm)
131"
(3327mm)
16-3/4"
(425mm)
1"
(25mm) TYP.
3"
(76mm)
7/8"
(23mm)
4-1/2"
(114mm)
C*