Liebert DS Network Card User Manual


 
Liebert DS Dimensions and Weights
24
Figure 19 Cabinet and floor planning dimensions—upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton),
all compressor models
Table 16 Weights for upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
Compressor Type
Dry Weight, lb (kg) approximate
Model 053 070, 077
Semi-Hermetic Compressor
Water/Glycol 2650 (1205) 2800 (1270)
GLYCOOL/Dual-Cool 2830 (1287) 2980 (1352)
Scroll or Digital Scroll Compressor
Water/Glycol 2370 (1075)
GLYCOOL/Dual-Cool 2550 (1157)
DPN001167
Rev. 1
Top View
Front View
High Volt Connection(s)
A
lternate Condenser
Fluid Piping Entrance
Low Volt
Connection(s)
Shaded area indicates a
recommended minimum
clearance for component
access.
3/4"
(19mm)
Bezels
35"
(889mm)
33"
(838mm)
76"
(1930mm)
2"
(51mm)
109"
(2769mm)
108"
(2743mm)
1-1/2"
(38mm)
24"
(610mm)
34"
(864mm)
Minimum required
for blower replacement
Required for
condenser cleanout
Note: Front air return unit shown. For rear return unit,
in addition to front service area shown, also include
25" (635mm) on one side of unit for access to rear return
filter box. See DPN001196, Figure 28.