Liebert DS Network Card User Manual


 
Liebert DS Dimensions and Weights
17
Figure 12 Cabinet and floor planning dimensions—downflow, air-cooled, 105kW (30 ton), all compressor
models
Table 9 Weights for downflow, air-Cooled, 105kW (30 ton), all compressor models
Compressor Type
Dry Weight, lb (kg) approximate
Model 105
Semi-Hermetic Compressor
Air-Cooled 3040 (1382)
Dual-Cool 3400 (1545)
Scroll Compressor
Air-Cooled 2920 (1327)
Dual-Cool 3280 (1491)
33"
(838mm)
35"
(889mm)
132"
(3353mm)
76"
(1930mm)
131"
(3327mm)
34" (864mm)
Shaded area indicates a
recommended minimum
clearance for component
access.
15"
(381mm)
3/4"
(19mm)
24-3/8"
(619mm)
102-13/16"
(2611mm)
Second Refrigerant
Piping Entrance
Air Inlet Opening
Opening
Opening
Bezels
Secondary Entrance
Low Volt Connections
Minimum required
for filter replacement
Secondary Entrance
High Volt Connection(s)
Top View
Front View
Notes: Filters are accessible
only through top of unit.
Downflow electrical
connections can be made
from top or bottom of unit.
DPN001012
Rev. 2