Mitsubishi Electronics A1SJ71AP23Q Network Router User Manual


 
App - 18
Appendix 5 Program for Refresh when Using Multiple Local Modules
Appendix 5.2 Program for refresh
APPENDICES
3) Refresh information table range of use
For local station No.4, all ranges are used.
For local stations No.5 to No.7, the area shown below is used.
Note that Presence or absence of refresh information table (Buffer
memory address: 0
H, 1H) uses the shaded parts in the figure below.
Table App.6 Refresh information table range for local stations No.5 to No.7
Address
Name
Hexadecimal Decimal
0H to 1H 0 to1 Presence or absence of refresh information table
2H 2
Refresh information table (First
half of link parameters)
Host station send
range in W
Start number (0 to FFF)
3H 3 Points (in units of words)
8H 8
Host station send
range in B
Start number (0 to FF0)
9H 9 Points (in units of words)
EH 14
Host station send
range in Y
Start number (0 to 7F0)
FH 15 Points (in units of words)
11H 17
Host station receive
range in X
Start number (0 to 7F0)
12H 18 Points (in units of words)
14H 20
Refresh information table
(Latter half of link parameters)
Host station send
range in W
Start number (0 to FFF)
15H 21 Points (in units of words)
1AH 26
Host station send
range in B
Start number (0 to FF0)
1BH 27 Points (in units of words)
Figure App.7 "Presence or absence of refresh information table" ranges for local stations No.5 to No.7
0: No setting, 1: Setting exists
Host station send range in W
Other station send range (1) in W
Other station send range (2) in W
Host station send range in B
Other station send range (1) in B
Other station send range (2) in B
Host station send range in Y
Host station receive range in X
First half of
link parameters
Host station send range in W
Other station send range (1) in W
Other station send range (2) in W
Host station send range in B
Other station send range (1) in B
Other station send range (2) in B
Latter half of
link parameters
Special relay (for link), special register (for link)
A
ddress: 0H
b15 b0b8 b7to to
(For system)
0: No setting, 1: Setting exists
Send range of master station for second tier
(first half) of B/W
A
ddress: 1H
b15 b0b2 b1to
Send range of master station for second tier
(latter half) of B/W
(For system)