Mitsubishi Electronics A1SJ71AP23Q Network Router User Manual


 
3 - 15
3.5 Buffer Memory List
3
SPECIFICATIONS
3.5 Buffer Memory List
The following shows a buffer memory list of a local module.
Table 3.10 Buffer memory list
Address
Name
Initial
value
Readable/
Writable*
1
Reference
section
Hexadecimal Decimal
0H to 1H 0 to 1 Presence or absence of refresh information table
0R
Section
3.6.2
2H 2
Refresh information
table (First half of link
parameters)
Host station send
range of W
Start number (0 to FFF)
Section
3.6.3
3H 3 Points (in units of words)
4H 4
Other station send
range (1) of W
Start number (0 to FFF)
5H 5 Points (in units of words)
6H 6
Other station send
range (2) of W
Start number (0 to FFF)
7H 7 Points (in units of words)
8H 8
Host station send
range of B
Start number (0 to FF0)
9H 9 Points (in units of words)
AH 10
Other station send
range (1) of B
Start number (0 to FF0)
BH 11 Points (in units of words)
CH 12
Other station send
range (2) of B
Start number (0 to FF0)
DH 13 Points (in units of words)
EH 14
Host station send
range of Y
Start number (0 to 7F0)
FH 15 Points (in units of words)
10H 16 System area (Use prohibited) - - -
11H 17
Host station receive
range of X
Start number (0 to 7F0)
0R
Section
3.6.3
12H 18 Points (in units of words)
13H 19 System area (Use prohibited) - - -
14H 20
Refresh information
table (Latter half of
link parameters)
Host station send
range of W
Start number (0 to FFF)
0R
Section
3.6.3
15H 21 Points (in units of words)
16H 22
Other station send
range (1) of W
Start number (0 to FFF)
17H 23 Points (in units of words)
18H 24
Other station send
range (2) of W
Start number (0 to FFF)
19H 25 Points (in units of words)
1AH 26
Host station send
range of B
Start number (0 to FF0)
1BH 27 Points (in units of words)
1CH 28
Other station send
range (1) of B
Start number (0 to FF0)
1DH 29 Points (in units of words)
1EH 30
Other station send
range (2) of B
Start number (0 to FF0)
1FH 31 Points (in units of words)
20H 32
Refresh information
table (Send range of
master station for the
second tier)
Send range of
master station for
second tier (first
half) of W
Start number (0 to FFF)
21H 33 Points (in units of words)
22H 34 Send range of
master station for
second tier (first
half) of B
Start number (0 to FF0)
23H 35 Points (in units of words)
24H 36 Send range of
master station for
second tier (latter
half) of W
Start number (0 to FFF)
25H 37 Points (in units of words)
26H 38 Send range of
master station for
second tier (latter
half) of B
Start number (0 to FF0)
27H 39 Points (in units of words)