10 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Error Contents
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
7148
H
Extension R block
No. error
A nonexistent extension file register block No. was
designated.
A block No. being used as an extension comment
area, sampling trace area, or status latch area was
designated.
PRO
Correct the designated block
No. and restart data
communications.
7149H System error The OS of the Q series C24 detected some error. ( 1)
714AH
Cannot execute a
command during
RUN
A write command was designated when "Disable
write during RUN" was set.
Parameter or sequence program was written during
RUN.
C/N
Change the setting to "Enable
write during RUN" and restart
data communications.
Stop the CPU and restart data
communications.
714BH
to
714D
H
System error The OS of the Q series C24 detected some error. ( 1)
714E
H
Monitor network
No. error
The written monitor network No. and the monitor
request network No. are different.
C/N
Check and correct the other
station access valid module No.
in the network parameters.
Rewrite the monitor data.
7150H System error The OS of the Q series C24 detected some error. ( 1)
7151
H
PLC No.
designation error
A PLC No. other than "FF" or "0 to 64(00
H
to 40
H
)"
was designated.
C/N
Check and correct the external
device transmit message and
restart data communications.
7152H System error The OS of the Q series C24 detected some error. ( 1)
7153H Frame length error
The received message length has exceeded the
allowable range.
CHn
ERR.
Review the transmission
message.
Correct the message format so
the number of access points is
within the allowable range.
7154
H
System error The OS of the Q series C24 detected some error. ( 1)
7155
H
Unwritten monitor
data error
Monitoring was requested before monitor data was
written.
PRO
Write the device to be monitored
before issuing a monitor
request.
7156
H
System error The OS of the Q series C24 detected some error. ( 1)
7160H PLC access error CPU model name cannot be confirmed. C/N
If there is an error in the CPU,
remove the CPU error and
restart data communications.
7161H
to
7163
H
System error The OS of the Q series C24 detected some error. ( 1)
7164H Request error
Either the request or the device designation method
is wrong.
Check the transmission
message/request from the
external device, make the
necessary corrections, and send
again.
7166
H
System error The OS of the Q series C24 detected some error. ( 1)
7167
H
A write command was designated when "Disable
write during RUN" was set.
C/N
Change the setting to "Enable
write during RUN" and restart
data communications.
7168
H
Cannot execute a
command during
RUN
A command that cannot be executed during RUN
was designated.
C/N
Stop the CPU and restart data
communications.
7169
H
CPU error Cannot communicate normally with the CPU. C/N
If there is an error in the CPU,
remove the CPU error and
restart data communications.
716AH
to
716C
H
System error The OS of the Q series C24 detected some error. ( 1)
716D
H
Monitor data was not written using QnA compatible
2C/3C/4C frame.
PRO
716E
H
Monitor data write
error
Monitor data was not written using A compatible 1C
frame.
PRO
Rewrite monitor data.