Mitsubishi Electronics QJ71C24N Network Card User Manual


 
10 - 19 10 - 19
MELSEC-Q
10 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Error Contents
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
7E6AH
Monitoring device
read point range
error
Read point of monitoring device is out of range.
Correct the setting value of the
read point of the monitoring
device.
7E6BH
7E6CH
7E6DH
CPU abnormal
monitoring setting
value error
Setting value (fixed value) of CPU abnormal
monitoring is out of range.
Correct the setting value (fixed
value) of the CPU abnormal
monitoring.
7E6EH System error The OS of the Q series C24 detected some error. ( 1)
7E6FH
Modem connection
error
Modem is connected to an incorrect channel.
Correct the CH to which
notification is sent.
7E70H CPU error
The communication with the CPU could not be
performed normally.
C/N
If there is an error in the CPU,
eliminate the error on the CPU
side and communicate again.
7E81H
to
7E8E
H
7EC1
H
7EC2H
System error The OS of the Q series C24 detected some error. ( 1)
7EC3H
Double send
request error
A send request was performed while another send
request was being processed.
Interlock (handshake) the send
requests.
7EC4H
Transmission data
count error
Transmission/
receipt buffer
setting error
Data larger than the transmit buffer size was
transmitted.
Transmission/receipt buffer settings out of range.
Make the transmission data
count smaller than the transmit
buffer size.
Make the non procedure
protocol transmit buffer size
larger.
Designate the first address and
size of transmission/receipt
buffer in the free area range of
the user.
7EC5H
Flash ROM access
error
Write to Flash ROM was requested when the setting
modification enable/disable switch in the GX
Developer was set to OFF.
When writing to Flash ROM, set
switch shown left of the given
interface to ON and restart the
Q series C24.
7EC6
H
Flash ROM access
error
There is an error in the Flash ROM read/write
request contents.
Check the read/write request
data and designate the correct
data.
7F00
H
System error The OS of the Q series C24 detected some error. ( 1)
The next data was received before processing of the
previous data was completed.
Increase the transmission time
by performing handshake with
the external device, etc.
7F01H Buffer full error
Multiple requests was simultaneously issued for one
channel.
Perform handshake with the
request source external device.
7F02
H
to
7F06
H
System error The OS of the Q series C24 detected some error. ( 1)
An ASCII code that cannot be converted to binary
code was received.
Check and correct the external
device transmit message and
restart data communications.
7F20
H
ASCII BIN
conversion error
An odd number of bytes of data was received during
data communications using ASCII
BIN
conversion.
PRO
When communicating using
ASCII BIN conversion,
always transmit the data in even
number bytes units.
There is an error in the command (frame) part.
7F21
H
Receive header
area error
An ASCII code that cannot be converted to binary
code was received.
PRO
Check and correct the external
device transmit message and
restart data communications.
7F22
H
Command error
A nonexistent command or device was designated.
The remote password length is wrong.
PRO
Check and correct the external
device transmit message and
restart data communications.
7F23
H
MC protocol
message error
There is no data (ETX, CR-LF, etc.) following the
character area, or designation was incorrect.
PRO
Check and correct the external
device transmit message and
restart data communications.