3 - 23 3 - 23
MELSEC-Q
3 SPECIFICATIONS
Address
Decimal (Hex)
Applicable
protocol
CH1 CH2
Application Name
Initial
value
MC Non Bi
Registration
allowed/not
allowed
Reference
section
Switch setting error and mode switching error status
0: No error
Other than 0: Switch setting error and mode switching error
515
(203
H
)
For confirmation
of switch setting
and mode
switching
CH1 Communication protocol setting No. (b0)
0: Normal 1: Error
CH1 Communication rate setting (b1)
0: Normal 1: Error
CH1 Setting change prohibit time mode switching (b3)
0: Normal 1: Error
CH2 Communication protocol setting No. (b4)
0: Normal 1: Error
CH2 Communication rate setting (b5)
0: Normal 1: Error
CH2 Setting change prohibit time mode switching (b7)
0: Normal 1: Disable
Setting station No. (b14)
0: Normal 1: Out of range
Linked operation setting (b15)
0: Normal 1: Error
0R
Not allowed
Section 4.3
Section
4.5.2
Section
8.6.9
Number of registered user frames
516
(204
H
)
0
H
: No registration 1 or more: Number of registered frames
User frame registration status (for confirmation of registration No.)
0: No registration 1: Registered
517 to 541
(205
H
to 21D
H
)
Bit corresponding to registration No. is 0(ON)/1(OFF).
Registration No.3E8
H
(1000) : Address 205
H
(b0) to
Registration No. 4AF
H
(1199) : Address 211
H
(b7)
Section
8.6.9
542
(51E
H
)
For confirmation
of user frame
Number of registered default registration frames (for system)
Depends
on
registration
status
R Not allowed
Section
8.6.9
Section
9.1.2 of
User's
Manual
(Application)
543
(51F
H
)
Use prohibited System area
Flash ROM system parameters write result
544
(220
H
)
For confirmation
of flash ROM
write result
0 : Normal completion
Other than 1 (error code) : Abnormal completion
RW Not allowed
Section
8.6.9
Modem function error code (error code when modem function is
being used)
545
(221
H
)
0 : Normal completion
Other than 1 (error code) : Abnormal completion
Modem function sequence status
546
(222
H
)
0: Idle
1: Waiting for initialization
2: Initializing modem
3: Waiting
4: Checking password
5: Communicating
6: Notification in progress
7: Modem disconnected
8: Callback Request reception waiting
9: Callback Modem disconnect waiting
10: Callback Delay time waiting
11: Callback Reconnecting
12: Callback Rechecking password
Number of data registration for connection
547
(223
H
)
0: No registration 1 or more: Number of registration
Data registration status for connection
(for confirmation of registration No.)
0: No registration 1: Registered
548 to 549
(224
H
to 225
H
)
Bit corresponding to registration No. is 0(ON)/1(OFF).
Registration No. BB8
H
(3000) : Address 224
H
(b0) to
Registration No. BD5
H
(3029) : Address 225
H
(b13)
Number of data registration for initialization
550
(226
H
)
For confirmation
of modem
function
0: No registration 1 or more: Number of registrations
0
R Not allowed
Section
8.6.2
Chapter 3
of User's
Manual
(Application)