Omron CJ1W-ETN21 Network Card User Manual


 
185
FINS/TCP Method Section 7-4
Example 2: Host Computer and Remote Node Connected Via Relay Node
(Ethernet Unit)
Destination IP Address: 196.36.32.100 (Ethernet Unit of relay node)
UDP port number: FINS UDP port number (Ethernet Unit of relay node)
FINS addresses (Remote node CPU Unit):
Network address: 2
Node address: 1
Unit number: 0
FINS addresses (Host computer):
Network address: 1
Node address: 50
Unit number: 0
FINS/TCP Sample
Program
Operation Overview This program reads 150 words of the PLC memory beginning at D00100
by sending a FINS command (MEMORY AREA READ, command code
0101) from a UNIX workstation (WS) to the PLC on the Ethernet network.
If no response is received within two seconds of sending the FINS com-
mand, an error will occur.
Settings The Ethernet Unit IP address is 196.36.32.100, and the FINS node
address is 100.
The FINS TCP port number at the Ethernet Unit (server side) is 9600
(default).
The workstation’s IP address is 196.36.32.50 and the FINS node address
is allocated automatically.
The FINS TCP port number at the workstation (client side) can be user-
set (if set to 0, the system automatically allocates an available port).
Host computer
IP address: 196.36.32.50
FINS network address: 1
FINS node address: 50
FINS unit number: 0
Relay node
IP address: 196.36.32.100
Ethernet
Remote node
FINS network address: 2
FINS node address: 1
FINS unit number: 0
Controller Link
Ethernet
Unit
Controller Link
Unit