Omron CJ1W-ETN21 Network Card User Manual


 
59
Remote Mail Command Details Section 3-4
FinsSend (FINS Command Send)
Function Requests execution of the specified FINS command by the Ethernet Unit.
Command Format
Response Format
3-4-2 Response List
Subject: FinsSend
Notation Description Omission
Body: Para1:FINS header
Example)
Specifying DNA=01, DA1=02, and
DA2=00:
Para1:010200
Enter the desired FINS header val-
ues for DNA, DA1, and DA2.
Note If this parameter is omitted, a
parameter error will occur.
Cannot be omitted.
Para2:Command code and
parameter
Example)
Specifying 0501:
Para2:0501*
Enter the command code and
parameter.
*: Always specify this as a termina-
tor.
Note If this parameter is omitted, a
parameter error will occur.
Cannot be omitted.
Attached file: None
Subject: Re:FinsSend
Response contents Description
Body: Response Code:@@@@ Refer to 3-4-2 Response List.
Response Status:@@@@ Refer to 3-4-2 Response List.
-- (FINS header) -- The FINS response is entered in the e-mail body.
-- (Response data) -- The FINS response is entered in the e-mail body.
Attached file: None
Response
Code
Response Status Description
0000 Normal completion Command completed normally.
F101 E-mail size exceeds than the
maximum size.
The e-mail is too large.
F102 E-mail address error Specified e-mail address is invalid.
F103 Invalid command Specified command is invalid.
F104 Protected (Command type) Specified command is disabled in the
protection settings.
F105 Invalid subject Specified subject is invalid.
F201 Invalid parameter Specified parameter is invalid.
F301 Decoding error Decoding error
F302 Invalid attached file Attached file is invalid.
F303 Attached file does not exist No attached file