Xantrex Technology XFR 2800 Power Supply User Manual


 
Features and Specifications
Specifications
30 Operating Manual for XFR 2.8kW Series Power Supply
Additional
Specifications
Input
Conditions
Figure 1.5 Typical Input Current Characteristics
(Based on 100 V, 28 A model.)
Rise Time (No Load, Full Load):
1
7.5 V to 60 V models: 100 ms;
100 V to 600 V models: 170 ms
Fall Time (No Load):
1
4 s
Fall Time (Full Load):
1
7.5 V to 60 V models: 100 ms;
100 V to 600 V models: 170 ms
Voltage Mode Transient Response:
2
<3 ms
Time Delay from power on until
output stable
7 s maximum
1. Measured with stepped 0-10 V analog programming source and a resistive load.
2. Time for the output voltage to recover within 0.5% of its rated value after a step change
in load current of 10% to 90% of rated output with an output setpoint between 50-100%
of rated value. Load slew rate <6 A/ms.
Rated AC Input Voltage 200/208/220/230/240 Vac (nominal)
Maximum AC Input Power 5000 VA
Operational AC Input Voltage 190-264 Vac
, 1φ (24.3 A maximum at 208 Vac;
22.4 A maximum at 230 Vac.)
Auto range select function.
Input Frequency Range 47-63 Hz
Power Factor 0.65 typical
I
N
P
U
T
C
U
R
R
E
N
T
(A)
O
U
T
P
U
T
C
U
R
R
E
N
T
30
25
20
15
10
5
0
50% 100%
OUTPUT VOLTAGE
100% at 190 Vac
100% at 264 Vac
50% at 190 Vac
50% at 264 Vac