Installation
Load Connection
Release 2.1 49
150 V to 600 V Models
The 150 V to 600 V models have a 4-terminal, wire clamp output connector. See
Figure 2.6 for a labelled drawing of the wire clamp connector. To prepare and
connect the load wiring:
1. Strip 0.4 in. (10 mm) at the ends of the wires.
2. Remove the top part of the output cover. Do not remove the chassis-mounted
part of the cover.
3. Loosen wire clamp screws (part of strain relief). Do not disassemble the strain
relief.
4. Insert load wire in strain relief.
5. To connect the wiring, loosen each terminal screw, insert a stripped wire into the
terminal, and tighten the screw securely.
6. Tighten the strain relief clamp.
7. Replace the top cover.
Figure 2.6 Output Voltage Connector
(For 150 V to 600 V models.)
WARNING
To protect personnel against accidental contact with hazardous voltages, ensure
that the load, including connections, has no live parts which are accessible. Also
ensure that the insulation rating of the load wiring and circuitry is greater than or
equal to the maximum output voltage of the power supply.
Negative Output/Return (–)
Positive Output (+)