Xantrex Technology XFR 2800 Power Supply User Manual


 
Remote Operation
Remote Analog Programming of Output Voltage and Current Limit
76 Operating Manual for XFR 2.8kW Series Power Supply
Table 4.2 Power Supply Settings for Different Programming Sources
Output
Voltage
Programming
Source
Output Current Limit Programming Source
0-5 Vdc 0-10 Vdc 0-5 k Resistor 0-10 k Resistor
None (Front
Panel Control)
0-5 Vdc SW1:
set 3 and 4
open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 3 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 2 closed, 3
and 4 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 2 closed, 3
open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 3 open.
J2: jumper 1 to
3.
0-10 Vdc SW1:
set 4 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
default settings.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 2 closed,
4 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 2 closed.
J2: jumper 1 to
3 and 2 to 3.
SW1:
default settings.
J2: jumper 1 to
3.
0-5 k Resistor SW1:
set 1 closed,
3 and 4 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 1 closed,
3 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 1 and 2
closed,
3 and 4 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 1 and 2
closed, 3 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 3 open,
1 closed.
J2: jumper 1 to
3.
0-10 k Resistor SW1:
set 1 closed,
4 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 1 closed.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 1 and 2
closed, 4 open.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 1 and 2
closed.
J2: jumper 1 to
3 and 2 to 3.
SW1:
set 1 closed.
J2: jumper 1 to
3.
None (Front
Panel Control)
SW1:
set 4 open.
J2: jumper 2 to
3.
SW1:
default settings.
J2: jumper 2 to
3.
SW1:
set 2 closed,
4 open.
J2: jumper 2 to
3.
SW1:
set 2 closed.
J2: jumper 2 to
3.
SW1:
default settings.
J2: no jumper.