Xerox 180 NPS Printer User Manual


 
XEROX DOCUPRINT NETWORK PRINTER SERIES INSTALLATION PLANNING GUIDE FOR MODELS 96/4635/180 NPS 6-1
6. 6Printer specifications and
requirements
This chapter provides power and space requirements for your
96/4635/180 printer. It also provides printer environmental
specifications.
For facts about controller power and space requirements, refer to the
Controller specifications and requirements chapter of this guide.
Power requirements
Your 96/4635/180 printer has important power requirements that
must be accommodated. These requirements are summarized in the
table below. For further details on power requirements, refer to the
voltage charts and wiring diagrams that follow.
For details on controller power requirements, refer to the Controller
specifications and requirements chapter of this guide.
Agency certification: UL 478 and 1950, IEC 950, CE Mark,
CSA 22.2 #220-1986, FCC (Class A), and VDE 0871 (Class A).
Table 6-1.Printer electrical requirements
Printer Voltage
Amp.
service KVA rating NEMA
Printer 60 Hz
(U. S. and Canada)
180
(Dual
cords)
120/240 VAC or 120/208 VAC
(Cord 1)
120/240 VAC or 120/208 VAC
(Cord 2)
50 amp
(Cord 1)
30 amp
(Cord 2)
Operating: 7.3
+ .75 per middle
module stacker
14-50R
(Cord 1)
14-30R
(Cord 2)
96/4635 120/240 VAC or 120/208 VAC 50 amp Operating: 7.3
+ .75 per middle
module stacker
14-50R
Printer 50 Hz
DELTA
180
4635
96
220, 230, 240 VAC
(3 phase, 4 wire)
30 amp Consult local
service rep.
WYE
(Star)
180
4635
96
380, 400, 415 VAC
(3 phase, 5 wire)
20 amp Consult local