Xerox 180 NPS Printer User Manual


 
PRINTER SPECIFICATIONS AND REQUIREMENTS
6-2 XEROX DOCUPRINT NETWORK PRINTER SERIES INSTALLATION PLANNING GUIDE FOR MODELS 96/4635/180 NPS
Outlet configurations
This section discusses specifications for system outlets and the
required wall outlet configurations for the USA / Canada and
internationally.
Note: All power outlets must be dedicated to this equipment. When
determining the electrical connections for your printer, make sure
that:
Each power cord has a separate circuit
The printer power cord configurations match your receptacle
Your electrical outlets are within the required specifications.
50 Hz systems: Ensure that power connections are per local codes/
regulations.
Printer outlet voltages60 Hz
The following table shows the voltages for the outlets on your printing
system. All power outlets must have a dedicated circuit for each
system equipment piece. Make sure each power cord has a separate
circuit.
Table 6-2.Printer (60 Hz) voltage requirements at power outlet
Service outlet
configuration Measurement of wiring Nominal Range
4 Wire Line 1 to neutral 120 V RMS 107-127 V RMS
4 Wire Line 2 to neutral 120 V RMS 107-127 V RMS
4 Wire Neutral to ground 0 0-10 V RMS
4 Wire Line 1 to line 2 208 V RMS 182-220 V RMS
4 Wire Line 1 to line 2 240 V RMS 210-254 V RMS