AEG Thyro-P Network Cables User Manual


 
30
Remarks
Parameters
Main menu
= Main menu (appears after plugging in the LBA)
Submenu
Menu
next
submenu
Default
Value
User
Value
6 Temperature
PT1000,PT100,NTC PT1000 Sensor used
Ch.curve no. X type Type-dependent, see chapter type overview
Temperature xxx°C Display actual temperature (relative value)
Lev.wire br. *
Lev. sh-circ. *
Comp.val.DAC *
7 No.,DaLo,K1,K2,K3 Status- / fault name
1 Communication with RS 232 active
2 Communication with fibre optic active
3 Power value negative
4 Communication fault RS 232 or fibre optic
5 Synchr. interfaces failure (e.g. Profibus)
6 External processor on the SSC signals fault
7 K3 after RESET
8 RESET active
9 Data in EEPROM invalid (reload parameters)
10 Internal message
11 x K2 Limiting value is exceed
12 Excess device temperature is present
13 Instant current interruption has responded
14 Internal message
15
Fault exists in load circuit-collective fault 16,17
16 Undercurrent exists in the load circuit
17 Overcurrent exists in the load circuit
18 Internal message
19 x Dalo Circuit OK
20 Undervoltage exists in the power section
21 Overvoltage in the power section
22 Internal message
23 Internal message
24 x K1 Synchronization fault
25 Collective fault 4,6,9,10,11,12,14-24
(each fault leads to switching)
26 Internal message
27 Internal message
28 Internal message
29 Internal message
30 Power Controller is in peak current limitation
(only for operating mode MOSI)
31
Temperature sensor, short circuit or sensor break
Controls Parameterization control characteristic
U
load
^
2
UxU UxU Selection control characteristic U
load
2
U
load
rms
U Selection control characteristic U
load
I
load
^
2
IxI Selection control characteristic I
load
2
I
load
rms
I Selection control characteristic I
load
Active power P
Selection control characteristic effective load, P
No control
Selection set operation (phase-angle control angle)
PID factors 8
Parameterization controller parameters, password prot.
8 PID factors
Sta.-Regl. OFF,ON ON
With standard control OFF the control parameters
can be stipulated
P - part type Controller parameters, P-part
I - part type Controller parameters, I-part
D - part type Controller parameters, D-part
* password protection