THYRO-P (HF-TYPES) TYPE CURRENT AIR VOLUME SOUND PRESS.
50HZ 60HZ IN 1 M DIST.
I [A] I [A] [M
3
/H] [DBA]
1P
200HF, 280HF 0.22 0.22 120 53
300HF, 495HF, 500HF, 650HF 0.50 0.38 150 67
780HF, 1000HF, 1400HF, 1500HF 0.55 0.60 580 75
2000HF, 2100HF, 2600HF, 2900HF 1.00 1.20 2200 81
2P
200HF, 280HF 0.50 0.38 200 67
300HF, 495HF, 500HF, 650HF 0.50 0.38 230 67
780HF, 1000HF, 1400HF, 1500HF 1.00 1.20 1200 81
1850HF, 2000HF, 2400HF, 2750HF 1.00 1.20 2100 81
3P
200HF, 280HF 0.50 0.38 260 67
300HF, 495HF, 500HF, 650HF 1.20 0.85 450 72
780HF, 1000HF, 1400HF, 1500HF 1.00 1.20 1600 81
1700HF, 1850HF, 2200HF, 2600HF 1.00 1.20 2000 81
The ventilators (with HF types) must run with Thyro-P switched on.
Connection according to connecting diagrams.
Longer cooling fan start-up times can be expected when operating.
Thyro-P at temperatures below 10° C. Therefore the adjustment range of upstream protection
devices should be at least the 2-fold of the indicated steady current.
TABLE TERMINAL SCREWS THYRO-P 1P, 2P, 3P CONNECTOR EARTHING SCREW
U1, V1, W1, U2, V2, W2
37H, 75H M 6 M 6
80H M 8 M 10
110H M 6 M 6
130H, 170H M 8 M 10
200HF, 280HF, 300HF M 10 M 10
495HF, 500HF, 650HF
780HF, 1000HF, 1400HF, M 12 M 12
1500HF, 1700HF, 1850HF,
2000HF, 2100HF, 2200HF,
2400HF, 2600HF, 2750HF,
2900HF
WITH UL APPLICATIONS
POWER CONNECTION
USE ONLY 60°/75°C COPPER CONDUCTORS (UL SPECIFICATION)
STUD TORQUE FOR SCREW MIN RATED MAX
TABLE TERMINAL SCREWS M 2 0.2 0.25 5.9
[Nm] M 6 3.0 4.4 22.5
M 8 11.5 17.0 44
M 10 22.0 33.0 75
M 12 38.0 56.0 75.0
[Pound inches] SCREW MIN RATED MAX
M 2 1.9 2.2 2.5
M 6 26.1 38.9 52.2
M 8 101.8 150.5 199.1
M 10 194.7 292.1 389.4
M 12 336.3 495.6 663.8
VENTILATOR 230 V,
50-60 HZ