AEG Thyro-P Network Cables User Manual


 
84
Due to European harmonization and international reconciliation, the standards will be subject to
years of adjustment and renumbering. The detailed schedule therefore contains the current stan-
dards as well, even if the date for their expiry has already been set. There is no product norm for
Thyristor Power Controllers, so that a sensible norm structure must be created from the correspon-
ding basic norms, which ensures safe application and opportunity for comparison.
CAUTION
Thyristor Power Controllers are non-valid devices for disconnection and may therefore be operated
only in connection with a suitable mains isolating device (for instance switch) connected on line side.
Approvals and conformities are available for Thyro-P:
• Quality standard according to ISO 9001
• Registration in acc. to UL 508, fi le no. E 135074
Investigated under consideration to Canadian National Standard C22.2 No. 14-95
• UL Markings:
· Field wiring terminal markings (see Chapter 4. „External Connections“)
· Use 60/75°C Copper Conductors only
· Tightening torque (pound inches) see Chapter 10. „Technical data“
· Devices are suitable for the following short circuit current ratings:
Devices rated 300A
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical
Amperes, xxx Volts Maximum, When Protected by RK5 Class Fuses, sized max. 600A / 600V“
Devices rated 495A and 695A:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical
Amperes, xxx Volts Maximum“
NOTE:
xxx = max. allowable voltage depending upon rating of the device
· „Branch circuit protection must be provided and sized according National Electrical Code and
any additional local codes“
• CE conformity
Low Voltage Directive 73/23 EEC;
EMV Directive 89/336 EEC;
Marking Directive 93/68 EEC
• Interference suppression
The RegTP confi rms the compliance with the interference suppression regulations for the power
control device
13. APPROVALS AND CONFORMITIES