Switched Rack PDU User Guide113
Verifying Upgrades and Updates
Verify the success or failure of the transfer
To verify whether a firmware upgrade succeeded, use the xferStatus command in the command line
interface to view the last transfer result, or use an SNMP GET to the
mfiletransferStatusLastTransferResult OID.
Last Transfer Result codes
Verify the version numbers of installed firmware.
Use the Web interface to verify the versions of the upgraded firmware modules by selecting the
Administration tab, General on the top menu bar, and About on the left navigation menu, or use an
SNMP GET to the MIB II sysDescr OID. In the command line interface, use the
about command.
Code Description
Successful The file transfer was successful.
Result not available There are no recorded file transfers.
Failure unknown The last file transfer failed for an unknown reason.
Server inaccessible The TFTP or FTP server could not be found on the network.
Server access denied The TFTP or FTP server denied access.
File not found The TFTP or FTP server could not locate the requested file.
File type unknown The file was downloaded but the contents were not recognized.
File corrupt The file was downloaded but at least one Cyclical Redundancy Check (CRC) failed.