APC AP89XX Power Supply User Manual


 
Switched Rack PDU User Guide49
tempHigh
Access: Administrator, Device User
Description: Set or view the high-temperature threshold in either Fahrenheit or Celsius.
Example 1: To set the high-temperature threshold to 70º Fahrenheit, type:
apc> tempHigh F 70
E000: Success
Example 2: To view the high-temperature threshold in Celsius, type:
apc> tempHigh C
E000: Success
21 C
Example 3: To view the high-temperature threshold of guest Rack PDU 2 in Fahrenheit, type:
apc> tempHigh 2:F
E000: Success
85 F
tempMax
Access: Administrator, Device User
Description: Set or view the max-temperature threshold in either Fahrenheit or Celsius.
Example 1: To set the max-temperature threshold to 80º Fahrenheit, type:
apc> tempMax F 80
E000: Success
Example 2: To view the max-temperature threshold in Celsius, type:
apc> tempMax C
E000: Success
27 C
Example 3: To view the max-temperature threshold of guest Rack PDU 3 in Fahrenheit, type:
apc> tempMax 3:F
E000: Success
95 F
tempReading
Access: Administrator, Device User, Outlet User
Description: View the temperature value in either Fahrenheit or Celsius from the sensor.
Example 1: To view the temperature value in Fahrenheit, type:
apc> tempReading F
E000: Success
51.1 F
Example 2: To view the temperature value of guest Rack PDU 3 in Celsius, type:
apc> tempReading 2:C
E000: Success
23.5 C