Switched Rack PDU User Guide65
Typical outlet group configurations
The following configuration shows two Rack PDUs, each with eight outlet groups. Each outlet group
consists of a single global outlet. Each outlet group
on the first Rack PDU is linked to the outlet group
in the same location on the second Rack PDU. One power cord of a dual-corded server
is
connected to each outlet on the first Rack PDU, and its other cord is connected to the corresponding
outlet on the second Rack PDU, ensuring that output power from both power sources to the server will
turn on or off in a synchronized manner in response to an outlet control action.
The following configuration shows three sets of synchronized outlets. Global outlets are shown in black.
Outlet groups are enclosed in red rectangles.
These four global outlet groups synchronize a total of 19 outlets.
These two global outlet groups synchronize 6 outlets, 2 in one group
and 4 in the other.
This local outlet group synchronizes 3 outlets on the same Rack PDU.