44Switched Rack PDU User Guide
olReboot
Access: Administrator, Device User, and Outlet User, but only for outlets to which the user is assigned.
Description: Cycle power to an outlet or group of outlets without any delays. If more than one outlet is
specified, then those outlets will be cycled together.
Example: To reboot outlets 3 and 5 through 7, type:
apc> olReboot 3,5-7
E000: Success
olStatus
Access: Administrator, Device User, and Outlet User, but only for outlets to which the user is assigned.
Description: View the status of specified outlets.
Example 1: To view the status for outlets 3 and 5 through 7, type:
apc> olStatus 3,5-7
E000: Success
3: BobbysServer: On
5: BillysServer: Off
6: JoesServer: Off
7: JacksServer: On
Example 2: To view the status for outlets 5 through 7 on guest Rack PDU 2, type:
apc> olStatus 2:5-7
E000: Success
5: Outlet 5: On
6: Outlet 6: On
7: Outlet 7: On
Argument Definition
all All device outlets.
<outlet name> The name configured for a specific outlet. (See “olName” on page 40.)
<outlet#> A single number or a range of numbers separated with a dash, or a comma-
separated list of single outlet numbers and number ranges.
Argument Definition
all All device outlets.
<outlet name> The name configured for a specific outlet. (See “olName” on page 40.)
<outlet#> A single number or a range of numbers separated with a dash, or a comma-
separated list of single outlet numbers and number ranges.