Switched Rack PDU User Guide27
resetToDef
Access: Administrator only
Description: Reset all parameters to their default.
Example: To reset all of the configuration changes except the TCP/IP settings for the Rack PDU, type:
resetToDef -p keepip
snmp, snmpv3
Access: Administrator only
Description: Enable or disable SNMP 1 or SNMP 3.
Example: To enable SNMP version 1, type:
snmp -S enable
system
Access: Administrator only
Description: View and set the system name, the contact, the location and view up time as well as the
date and time, the logged-on user, and the high-level system status P, N, A (see “About the Main Screen”
on page 15 for more information about system status).
Example 1: To set the device location as Test Lab, type:
system -l “Test Lab”
Example 2: To set the system name as Don Adams, type:
system -n “Don Adams”
Option Arguments Description
-p all | keepip Reset all configuration changes, including event actions, device settings, and,
optionally, TCP/IP configuration settings.
Option Arguments Description
-S enable | disable Enable or display the respective version of SNMP, 1 or 3.
Option Argument Description
-n <system name> Define the device name, the name of the person responsible for the
device, and the physical location of the device.
Note: If you define a value with more than one word, you must
enclose the value in quotation marks.
These values are also used by StruxureWare Data Center Expert and
the Rack PDU’s SNMP agent.
-c <system contact>
-l <system location>