Chapter 4: E2 Controller
4.9 BMS Parameters, Version 1.2
Table 4-27. BMS parameters.
Supported Protocols Speed Media Connection Notes
BACnet over IP 10 Mbps 10BASE-T RJ-45 direct unit connection Uses BMS addresses
BACnet over Ethernet 10 Mbps 10BASE-T RJ-45 direct unit connection Uses BMS addresses
HTTP 10 Mbps 10BASE-T RJ-45 direct unit connection Uses BMS addresses
SNMP V1, V2c 10 Mbps 10BASE-T RJ-45 direct unit connection Uses BMS addresses
Modbus over IP 10 Mbps 10BASE-T RJ-45 direct unit connection Uses Modbus addresses
BACnet MS/TP 19200 baud Twisted pair Daisychain connection Uses BMS addresses
Modbus RTU 19200 baud Twisted pair Daisychain connection Uses Modbus addresses