Black Box CRDX-W-FS-12KW Network Hardware User Manual


 
724-746-5500 | blackbox.com
Page 110
724-746-5500 | blackbox.com
Chapter 4: E2 Controller
4.9.6 Digital Input Packed Bit Variables
Table 4-34. Digital Input Packed Bit Variables.
Bit Digital Inputs 1 Digital Inputs 2
0 Remote shutdown Customer alarm 2
1 Customer alarm 1 Customer alarm 3
2 Water Reserved
3 Condensate pan Reserved
4 Humidifier Reserved
5 Moisture Reserved
6 Middle fan alarm Reserved
7 Upper fan alarm Reserved
8 Fire/smoke Reserved
9 Lower fan alarm Reserved
10 Dual power input A Reserved
11 Dual power input B Reserved
12 Circuit 1 low pressure Reserved
13 Circuit 1 high pressure Reserved
14 Pump alarm Reserved
15 Humidifier lockout Reserved