4.9.4 Alarm Packed Bit Variables
Table 4-32. Alarm-Packed Bit Variables.
Bit Alarms 1 Alarms 2 Alarms 3
0 Emergency shutdown Middle fan alarm Reserved
1 Remote shutdown Upper fan alarm Reserved
2 Customer Alarm 1 Lower fan alarm Reserved
3 Airflow High temperature Reserved
4 Filter Low temperature Reserved
5 Fire/Smoke High humidity Reserved
6 Water detection Low humidity Reserved
7 Condensate pan High water temp CW1 Reserved
8 Moisture Low water temp CW1 Reserved
9 Circuit 1 low pressure Customer Alarm 2 Reserved
10 Circuit 1 high pressure Customer Alarm 3 Reserved
11 Pump Flow alarm (temp sensors) Reserved
12 Dual power input A Flow alarm (flow switch) Reserved
13 Dual power input B Reserved Reserved
14 Humidifier Reserved Reserved
15 Loss of power Reserved Reserved